Ground source heat pumps When using prEN14825, data according to Table 13 has to be filled in. The chosen climate, “average” gives that Tdesign is -10°C. Tbivalent is the outdoor temperature where the capacity of heat pump covers the heat demand of the house. It is set to -10°C, to make the heat pump monovalent, like in the field study. TOL, the operation limit temperature, is set to -25°C. This temperature declares where the heat pump no longer can operate. The model calculates Pdesign as a result of Tbivalent and is the heat demand of the house at Tdesign.